ESIS New Website

DT500 Series Datataker Data Loggers
DT500, DT505,   DT600 and DT605


Esis Pty Ltd - Australia - Ph 02 9481 7420  Fax 02 9481 7267  www.esis.com.au 
E-mail: click here       Go to Esis main page

Jump up to Datataker general page


• General Purpose
     low cost Data Loggers
• 10-30 Sensor Channels,
• 7 Digital Channels
      (4xDIO, 3 High Speed Counters)
• Easily Configurable Software
• Stand Alone and
   Real Time Data Acquisition
• Remote Monitoring and Control
• PC Card for Data Storage
• Unique Universal Channels
• Removable Screw Terminals                                                            Close up picture of DT600 LCD and buttons  

The dataTaker DT500 Series
The dataTaker DT500 Series of general purpose, battery powered data acquisition and data logging systems measure inputs from most sensor types. Data can be conveniently and securely stored in battery backed RAM and removable memory cards. The dataTaker DT500 Series consists of four models:
DT500 Basic Unit with Solid State Channel Selector
DT600 Solid State Channel Selector & LCD Display and Keypad
The highest range of the DT500 and DT600 is ±2.5VDC.
The common mode range is ±3.5VDC, inputs are protected to ±5VDC

DT505 has Relay Channel Selector
DT605 has Relay Channel Selector & LCD Display and Keypad
The DT505 and DT605 also have a ±100VDC range, and on that input range the common mode range is also ±100VDC.

DT505 and DT605 look the same as DT500 and DT600
   - the difference is internal 

The DT600 and DT605 both have an integral display and keypad that allows users to view channel data, alarm status, and system information including time, battery status and amount of data stored.
Function keys allow keypad control over the unit's operation.

Datataker Windows Based Software
Datataker produces a range of Windows based software, which provides a simple interface for supervising the dataTaker DT500 Series.
Datataker's software allows you to manipulate data with statistical functions and calculations.  Alarms can be set for all channels, providing you with warning and control signals.

Datataker's Extensive Range
Datataker's extensive range of data acquisition and data logging systems are real time and stand alone, able to acquire, process and log data without direct computer control. The powerful yet easy-to-use hardware and software enables you to log a wide range of measurements and events.
More than 30,000 dataTakers are in use in over 55 countries - dataTakers are used in many applications including science, aerospace, mining, manufacturing, meteorology, agriforestry, hydrography, petrochemical, public utilities and transportation.

Applications for the dataTaker DT50 include:

• Fault Finding
• Monitoring Water Levels
• Process Monitoring
• Building Monitoring
• Automotive Testing
• Monitoring Climatic Conditions
• Machine Down Time Monitoring
• Product Testing
• Research & Development
• Flood Warnings

DT500 Tutorials

   DT500 Installation           DT500 DeLogger Software Tutorial

   DT500 Programming      DT500 Range Sensors

Analog Channels
Number of input channels
depends on sensor wiring configuration. Sensor configurations may be mixed.
Two wire: 10
Two wire with one terminal shared (common): 30
Three wire: 10
Four wire: 10

Expansion: by Channel Expansion Modules (CEM)

Multiplexer (Channel Selector)
DT500 and DT600: solid-state ±5V input protection
DT505 and DT605: relay ±100V input
Input impedance: 1Mohms or  >100Mohms,  programmable
Common mode range:DT500 and DT600: ±3.5V
DT505 and DT605: ±100V on 100V range

Sampling
Sampling for accuracy and noise rejection by integrating over 50/60Hz line period
Maximum sample speed: 25Hz
Effective resolution: 15 bits
Linearity: 0.01%
Common mode rejection 25mV range: >90dB
Line (50/60Hz) series mode rejection: >35dB

Sensor Excitation
Each channel: 4.5V, 250µA or 2.5mA
DC voltage: 5V at 100mA (max.) switched

Internal Channels
Temperature (thermocouple reference junction): 1
Reference voltage channels: 1
Internal battery voltage: 1


Sensor Support

Supports a wide range of sensors types including, but not limited to the following:

Thermocouples
Types: B, C, D, E, G, J, K, N, R, S, T
Reference junction compensation accuracy:
At case temperature 25°C: ±1.0°C       At case temperature range -20° to +60C: ±1.5°C

RTDs
Types: Pt (385 & 392), Ni, Cu
Resistance range: 10ohms to 2kohms
Measurement accuracy:4 wire: 0.15% of resistance value3 wire: 0.25% of resistance value

Thermistors
Types: YSI 400xx Series
Resistance range: <7kohms,
<20kohms with parallel resistor

Monolithic Temperature Sensors
Types supported: LM335, LM34, LM35, AD590

 

Bridge Sensors
Configurations: 4-wire and 6-wire
Excitation: voltage or current
Bridge completion: external or internal half bridge

4-20mA Current Loops
Shunt value: 100ohms to a shared common
Accuracy: 0.25% at 25°C

Sensors - Comments
A wide range of sensor scaling and linearizing facilities are provided including polynomials, expressions and functions

Digital Channels
Bi-directional channels: 4
Dedicated counter channels: 3
Digital Inputs:   4, shared with bi-directional channels
  Input Type: logic level (protected with pull-up)
Counter Channels:   4 low speed (10Hz) shared with bi-directional channels 3 high speed (1kHz, sleep mode) with switchable internal clocking options,   Size: 16 bit (65535 counts)
Digital Output:  4,   Output type: open-collector npn transistor,
    Rating: +30V, 100mA


Calculation Channels
Any expression involving variables and functions including: sin(), cos(), tan(), asin(), acos(), atan(), abs(), sqrt(), average, maximum, minimum, time of max., time of min., variance, integral, histogram

Scheduling of Data Acquisition
Number of schedules: 4 acquisition schedules, 1 immediate schedule, 1 alarm schedule
Scan triggers: time base or digital event
Conditional scanning: while digital input high
Time based scheduling: from seconds to months in increments of 1 second, 1 minute, 1 hour and 1 day
Maximum scheduled rate: 1 second or as fast as possible, typically 25 samples per second
Dynamic scan time base change: yes
Maximum number of channel entries: 110

Alarms
Condition: high, low, within range and outside range
Delay: optional time period for alarm response
Actions: set digital outputs, execute any dataTaker commands

Data Storage
Internal: Type: battery backed SRAM   
               Capacity: 166,500 data points
PC Card (PCMCIA Card)
Types: SRAM to 4MBytes, Type 1,    Card voltage: 5V types,  
            Capacity: up to 1,390,000 data points


Data format: proprietary,     
Download Data Format:  ASCII floating point, fixed point or exponential formats
Compatibility: spread sheets, word processors, graphing packages, statistical programs and SCADA software

Serial Interface (RS232)
The DT50 is programmed and data extracted via the RS232 serial interface
Speed: 300 to 9600 baud (9600 default),
Handshake: XON and XOFF
Wake from sleep: yes       
Isolation: 500V
Compatibility: computers, modems, satellite-modems, radio-modems and printers

Network Interface
Standard: RS485
Protocol: proprietary with error correction
Speed: 1200 Baud
Distance: 1000 meter maximum


System

Display and Keypad
Models: on DT600 and DT605 only
Type: LCD, 2 lines by 16 characters, back light
Display functions: channels data, alarms, battery status, data capacity
Key pad: 5 keys for scrolling, function execution
Beeper: for alarms, etc.
Indicator LED’s: 3 programmable

Real Time Clock
For time stamping of data, scheduling and timers
Normal resolution: 1 second
Accuracy: 2 seconds per day (25°C)

Power Supply
Voltage range: 11 to 24Vdc or 9 to 18Vac
External solar panel: 12V (0.4 x 0.4m typical size)
Power Consumption
In normal mode: 1W (2W with battery charging)
Sleeping: 2mW (350µA from battery)
Typical low power operation: 20mW
Internal Main Battery
Chemistry: lead acid gel cell
Voltage (capacity): 6V (1.2AHr)
Temperature compensation: –10°C to +70°C
Operating time: Normal: approximately 10 hours,
                   Low power: approximately 3 months
Internal Backup Battery
For real time clock and internal data storage backup
Type: 3V 1/2AA Lithium

Warranty
The dataTaker range is covered by a 3 year warranty on workmanship and parts.

Physical and Environment
Physical dimensions: 260 x 110 x 85mm(height 104mm with PC Card)
Weight: 2.2kg (4kg shipping)
Environment temperature range: –45°C to 70°C
Humidity: 85%RH, non-condensing
Environmental protection: IP45

Accessories Included
Line adaptor: 110/240Vac, 500mA
Battery: 6V 1.2AHr gel cell
Comms cable: for PC, with 9 to 25 pin adaptor
Software: Software Suite CD which includes DeLogger, DeTransfer, DePlot applications
Manuals: "Getting Started with dataTaker"
"dataTaker Manual"

Options & Accessories
Channel Expansion Module (CEM) Multiplexer: relay
   2 CEMs per DT500 Series unit
  Channel number:10 two wire30 two wire shared terminals
  20 digital inputs10 digital outputs, 5 with relay contacts

Portable Carrying Case (PE)
Capacity: 1 DT500 Series unit
Environmental protection: IP66
SRAM PC Card (MC1024P, MC4096P))
Capacity: 1MByte, approximately 340,000 readings
4MByte, approximately 1,390,000 readings

DeLogger™4 Pro Software
Graphical programming and supervision software. Supports a large network of DT500 Series units connected via modem. Features include comprehensive plotting, reporting, mimics, database, web publishing and other powerful capabilities.

Esis Pty Ltd - Australia - Ph 02 9481 7420  Fax 02 9481 7267  www.esis.com.au 
E-mail: click here       Go to Esis main page

Esis Pty Ltd, PO Box 450, Pennant Hills NSW 1715 Australia